100% Stator Ground Fault Protection of Alternators by Low Frequency Injection and Using Real Power Signal

DILSHAD, ARA HOSSAIN and MD MIZANUR, RAHMAN and S M, SALIM REZA and SAJIB, CHAKRABORTY and WAHIDUL, HASAN (2015) 100% Stator Ground Fault Protection of Alternators by Low Frequency Injection and Using Real Power Signal. In: Fourth International Conference On Advances in Computing, Electronics and Electrical Technology - CEET 2015, 26-27 September, 2015, Kuala Lumpur, Malaysia.

[img]
Preview
Text
20151005_044656.pdf - Published Version

Download (611kB) | Preview
Official URL: https://www.seekdl.org/conferences/paper/details/6...

Abstract

In this paper, 100% stator ground fault protection by application of low frequency (20 Hz) injection for 6.6/132 KV alternators have been investigated. Here, different types of faults of alternators and possible protections by conventional means have been discussed. It is shown why conventional method by differential relay protection is not adequate. Modern approach of alternator fault protection is reviewed and effective methods of 100% stator ground fault protection of alternators have been applied. In this work, it is focused protection of alternators based on sub-harmonic injection method using low frequency band pass filter. The design of stator ground fault protection consists of 20 Hz signal generator, band pass filter, 20 Hz current relay and protection system model includes alternator, total capacitance to ground of stator winding, grounding transformer turns ratio, and neutral resistor. PSPICE simulation of the protection scheme is performed and analyzed.

Item Type: Conference or Workshop Item (Paper)
Uncontrolled Keywords: Alternator; Generator; Filter; Stator; Pspise simulation
Depositing User: Mr. John Steve
Date Deposited: 26 Apr 2019 04:42
Last Modified: 26 Apr 2019 04:42
URI: http://publications.theired.org/id/eprint/1522